Three-Phase Series Reactor Tunes Capacitor Branch Below 5th Harmonic

Date:2026-11-18

A Three-Phase Series Reactor sits in line with the capacitor branch of a low-voltage power factor correction installation and does one job the capacitor cannot do for itself: it keeps harmonic current from loading the capacitor. Chengxi Electric Group Co., Ltd. builds this part as the CKSG series, a dry-type iron core reactor with a 7% reactance rate for 450 V systems, matched to capacitor branches from 5 kvar to 60 kvar.

What Harmonics Do to a Capacitor Branch

Variable-speed drives, rectifiers and UPS systems draw current in pulses, and that current concentrates at the 5th harmonic, which is 250 Hz on a 50 Hz network. A capacitor presents less impedance as frequency rises, so it draws harmonic current readily, and the inductance of the supply transformer can form a resonant circuit with the capacitor close to one of those harmonic orders. When that happens, the harmonic current in the capacitor exceeds the harmonic current the loads actually produce. The capacitor heats up, and premature failure follows. Without a reactor in the branch, nothing prevents that resonance from forming, and the capacitor absorbs the overload. A Three-Phase Series Reactor placed in the capacitor branch changes that circuit so it no longer resonates on the 5th harmonic.

How the Reactance Rate Sets the Tuning Point

The reactance rate of a Three-Phase Series Reactor is the reactor's reactance expressed as a percentage of the capacitor's reactance at the fundamental frequency. With a 7% rate, the series resonance of the reactor and capacitor falls at the fundamental frequency divided by the square root of 0.07. That is about 3.8 times the fundamental, or roughly 189 Hz on a 50 Hz system, and it sits below the 5th harmonic at 250 Hz. The tuning point depends on the ratio between the two reactances, which is why a Three-Phase Series Reactor is rated against the capacitor and not against the load current.

zYtib2

At 250 Hz the branch is above its own resonance, so the reactor and capacitor together behave inductively and the branch no longer amplifies 5th-harmonic current. The capacitor is protected from the harmonic overload that shortens its life. The same inductance limits the inrush current each time the branch is switched on, which eases the duty on the switching device as well. A Three-Phase Series Reactor with a 7% rate suits networks where the 5th harmonic dominates, and other reactance rates exist for networks whose dominant harmonic is a different order. The rate is therefore matched to the harmonic that is actually present in the installation.

Where the Reactor Belongs in a Plant

Variable-speed drives, rectifiers and UPS systems put 5th-harmonic current onto the busbar they share with the capacitor steps. Where capacitor steps sit on that busbar, each step is fitted with its own Three-Phase Series Reactor, so every capacitor branch is detuned individually and a step that switches in or out does not change the tuning of the others.

The CKSG Three-Phase Series Reactor range covers this duty from a small distribution board up to a large compensation cabinet. Each phase is a resin-impregnated coil wound on a laminated iron core, and the laminations limit eddy-current loss in a part that carries harmonic current continuously. The three phases are supplied as a matched set on a galvanised steel frame with colour-coded terminal lugs already fitted for direct cable or busbar connection, so the reactor goes into a cabinet as one assembly.

Pairing the Reactor With Its Capacitor

The rated capacity of the reactor is 7% of the capacitor branch rating, and the model number carries both values. CKSG-2.1/0.45-7% is the unit for a 30 kvar capacitor branch on a 450 V system, because 7% of 30 kvar is 2.1 kvar. The same arithmetic runs through the range: CKSG-0.35/0.45-7% matches a 5 kvar capacitor and CKSG-4.2/0.45-7% matches a 60 kvar capacitor, with nine models in total and the 10, 15, 20, 25, 30, 40 and 50 kvar steps between them.

A Three-Phase Series Reactor sized to the capacitor it protects keeps the tuning point where the calculation puts it. One that is too small for its capacitor tunes the branch higher than intended, and one that is too large tunes it lower, so the model number is read against the capacitor rating before the cabinet is wired. Chengxi supplies the CKSG Three-Phase Series Reactor on an OEM/ODM and wholesale basis.